CONDO OPERA OT

Catagory : Filter Housings
CONDO OPERA OT
LAMINAR FLOW UNIDIRECTIONAL OT FILTRATION MODULE | CASINGS
Laminar Flow Operation Theatre HEPA Housing with multiple arrays of HEPA filters with Diffusers for absolute Efficiency Filters.
PRODUCT SPECIFICATIONS | ||
---|---|---|
Category | Laminar HEPA Ceiling Terminal Module for Operation Theatre | |
Conformity Standards | ASHRAE / ASHE Standard-170; NFS 90-351 | |
Housing Box material | Stainless steel/ Galvanized steel or Mild Steel-Powder Coated. | |
Finish | SS 304/ RAL 9010 or equivalent grade to prevent corrosion | |
Design and Construction | As a single unit or as separate Modular Units. Each separate unit can be bolted together at site as a single unit. The joints are later mechanically sealed to be Leak proof & airtight. | |
Diffuser / Face Guard | Perforated type-SS Diffuser/ G.I or M.S Powder Coated. Fully Removable type or Hinged type. | |
Spigot connection | Lateral or Top spigot | |
Spigot | circular or Rectangular with Flanges | |
Central square or rectangular opening | For Surgical Light provision | |
Filter Installation & Mounting | Filter installed from room side by removing diffuser/ Hanging chains provided for hinged type diffuser. Filter locking using quarter turn locks or quick clamping mechanisms with gasket compression inbuilt. | |
Test port | Single Port per module to measure filter replacement pressure drop at site. | |
Pressure Monitoring | DP switch for signaling filter replacement | |
Hanging Clamps | Fully welded hanging Clamps used for ceiling suspension | |
Performance Testing | Each Laminar OT module shall be fully leak tested. All welds and penetrations shall be bubble tested for leaks and must meet zero leakage criteria. | |
HEPA Filter | Seamless PU Gasket type or Gel Seal type. Please refer Hepa filter technical catalogue for selection. | |
HEPA Grade as per EN 1822 | H14 | |
Maximum Final pressure drop of filter | 500 Pa |
APPLICATIONS
- Operation Theatres
- Infectious wards
- Delivery Rooms
- Neonatal units
- Intensive Care units
- immunosuppressed department
- Medical Labs
Features & Advantages
- The CONDO Opera OT modules is used in Operation Theatre for providing laminar flow filtered air.
- The Laminar flow Terminal modules are used as final filtration at room ceiling side with H14 grade HEPA filters.
- The laminar flow system complies with ASHRAE / ASHE Standard-170 and NFS 90-351.
- Optimal aseptic conditions are being achieved due to laminar air flow which is gradually directed toward exhaust openings.
- The Laminar OT improve quality and cleanliness of air in hospitals with the aim of avoiding pathogen transmission between patients and medical crew.
- The system is especially recommended for operating rooms with high aseptic conditions for conducting transplants, cardiac surgery, orthopaedics, neurosurgery, ophthalmic.
- The system can be built as a single element or as separate units for ease of handling, transportation, positioning and assembly at site.
- Recommended air flow velocity above operation table is between 30-50 fpm.
- The recommended Air change rate as per ASHRAE standard in operation theatre is 20 or higher for unidirectional flow. Recirculation unit is not recommended by ASHRAE.
- The height of the unit is 450 mm or above, depending on filter depth and spigot size.
- The spigot connections can be rectangular type or circular type. The rectangular spigot will have flanges to connect with duct work.
- The hood shall have channels to fix the HEPA filter. In case of Gel seal HEPA filter, integral knife edge shall be provided.
- The diffuser plate shall have hemmed edges.
- A wide range of HEPA filter choices based on airflow handling capacity and pressure drop criteria can be opted for.
- The HEPA filters are tested and certified as per EN 1822 and complies to ISO 14644 standard of testing.
- Filters are selected based on airflow, efficiency and pressure drop requirements.
- All the hoods shall be fully leak tested, visually inspected and tested as per the standards for the Zero leak performance.
- In house test certificates are provided for HEPA filter and housing Box certifying its leak proof performance.